Siemens Synova FC330A Manual page 8

Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

1.3
Summary of technical data FC330A-ECO... (1 loop)
Processing capacity
− Addressable Synova® detectors (SynoLOOP)
– Audible alarm devices
– Programmable driver outputs
– Programmable contact outputs
– Remote transmission outputs
– Text indicating panel
– Text control panel
– LED driver outputs
– Programmable control inputs
Power supply main board
mains side:
− operating voltage
− power consumption
low voltage side:
− system supply voltage
− max. current power supply
− built in emergency power battery
− total current available for all control and 24V outputs
− battery charger
− battery load test
− battery operation upon mains power failure
− battery low discharge cut off
Ambient conditions
Temperature
Humidity
IP protection category (EN 60529 / IEC 529)
Standard
Dimensions
Weight
Colour
− Control unit
− Operating panel (keyboard membrane)
Programming
4
Building Technologies
Fire Safety & Security Products
1
1
2
optional (K3G050)
+ 2
8
optional (K3G050)
+ 4
optional (K3G050)
8
optional (K3G060)
8x2x48
optional (K3I110)
16
2
optional (B3Q580)
...16
optional (B3Q59x)
...16
optional (K3R072)
8x2x48
4
optional (K3I110)
16
115 / 230V
max. 50VA
u 21,5 ...v 29,5V (temperature compensated)
limited at 1,5A
2 x 12V max. 12 Ah
0,5A
lead acid / 2 x 12V max. 12Ah
manually via operating menu / automatically 1 x per 24h
....72h, see page 106
v 21,8V
operation
0°C ... +50°C (VdS: +...40°C)
storage
−20°C ... +60°C
max. 95%, no condensation
according to IEC 721-3-3 class 3K5
IP40
EN 54-2: 1997
EN 54-4: 1997 / A1: 2002
EN 50130-4: 1995 + A1: 1998 + A2: 2003
EN 60950-1: 2001
EN 61000-6-3: 2001
W = 400mm
approx. 7,5kg without battery and optional modules
RAL 7035 light grey
Pantone 421C grey, 424C dark grey
on site with built-in operating panel or PC configuration tool
loop with max. 128 addr. devices or
stub line with max. 32 addr. devices
monitored control lines max. 0,5A/24V
ratings max. 48mA/24V
DC
ratings max. 1A/30V
DC
external
external, ratings max. 1A/30VDC
contacts ratinged at max. 1A/30V
LCD
LCD
external
external, only for detector zones
"15% (VdS: +10%) 50...60Hz
AC
H = 400mm
D = 170mm
DC
DC
1583_o_en_−−_1
08.2005

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents