Siemens Synova FC330A Manual page 59

Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

Example
− Typical floor layout with linked devices
− Presentation of 'alarm event' in room 104
1st line zone no. and element no.
2nd line individual user text
ALARM zone ###/## / ######
2nd floor room office 104
Room
101
ZONE
zone 1
ELEMENT
01
DEVICE
Building Technologies
Fire Safety & Security Products
is part of the system configuration. Each installation has its specific zoning. The zoning
requires the knowledge of the precise order of installation of all devices within the line(s).
ZONE
− represents the 'room-address'
− alarm events are shown on the 'zone level'
− each zone has its own user text
− is part of the logical structure
ELEMENT
− represents the 'detector-address' within a zone
− is always allocated to a zone (automatically done during the linking 'device to zone')
− can have its own user text instead of the ZONE user text (only in special cases)
DEVICE
− physical device (detector, call point, etc.) within the detection line
− each device must be linked to a zone
− is part of the physical structure
1 (1)
Room
Room
102
103
zone 2
zone 3
01
01
linking
1
2
installed detector line/loop
room 101
zone 1
1
room 102
zone 2
room 103
Room
104
zone 4
01
02
3
4
5
room 104 zone 4
8
9
element 01 + 02
7
2nd floor
6
2
3
4
zone 3
Corridor
zone 5
01
02
03
6
7
5
Elevator
zone 6
01
8
9
55
1583_o_en_−−_3
08.2005

Hide quick links: