Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

multiple faults on line ##
NEW device > line ##
No resp. from LON−interface card
OPEN CIRCUIT in horn−line ##
OPEN CIRCUIT RT−alarm
OPEN CIRCUIT RT−fault
paperOUT/powerOFF printer (code #)
Power FAULT in FBF
Power supply mismatch
printer in mode 'off line'
read/write ERROR flash−EPROM #
RESTART due to manual initiation
RESTART due to power down
RESTART due to system fault
RESTART due to watchdog: Part #
RESTART due to wrong CHECKSUM
RESTART due to soft err. File ###
Sabotage FAULT, door open on FSD
Sequence error at LON dev. ##
short at term A of line ##
short at term B of line ##
short at term A and B of line ##
SHORT CIRCUIT > line ##
120
Building Technologies
Fire Safety & Security Products
Several faults on the addressable line simultaneously.
% disconnect line then re-connect section by section
New device within the displayed line inserted.
% check and adapt configuration
No communication to RS232/LON card K3I080
% check connection
Control line 'horn' either short circuit, reversed polarity or miss-
ing blocking diode to sounder(s).
% check wiring of sounder(s)
Control line 'remote transmission ALARM' either short circuit,
wrong polarity or missing diode to load.
% check wiring
Control line 'remote transmission FAULT' either short circuit,
wrong polarity or missing diode to load.
% check wiring
Printer disconnected or locally turned off.
% reconnect or turn on printer or replace paper
then % reset fault
VdS card K3L070 is out of power.
% check fuse on K3L070
Jumpers 'ST11...14' not set correctly.
% check jumpers 'ST11...14' on K3X...
Printer locally turned off or unpowered or, depending on printer
type, also run out of paper.
% check printer % then reset
Read /Write problem on FLASH−EEPROM.
% restart system, if still reported replace K3X...
Normal procedure after manual restart with switch 'S1'.
% reset
System stop due to disconnection by 'low discharge protec-
tion' (= mains failure and battery <22.5V ).
% restore mains supply % reset
General system fault (also appears when system has been
out of order and is put back into operation again).
% reset (
if this is taking place frequently
Restart due to software or hardware error.
% reset
(if this is taking place frequently
Periodical test of user data is negative.
% reset
(if this is taking place frequently
Indicates a software problem.
% note "file ###" if it occurs several times, contact the hotline
Door at FSD open (only with VdS card).
% go to location of FSD and check situation
Fault on the LON-bus for short time.
% if frequent contact hotline
Short circuit at the beginning of the addressable line on K3X...
% check field wiring and corresponding device
Short circuit at the end of the addressable line on K3X...
% check field wiring and corresponding device
Short circuit at the beginning and at the end of the addressa-
ble line K3X...
% check field wiring and corresponding device
Short circuit within the indicated line.
% wait until device address is displayed
%
replace K3X...)
%
replace K3X...)
%
replace K3X...)
1583_o_en_−−_7