Siemens Synova FC330A Manual page 122

Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

Error:Checksum fault in area: ###
Error:Mod.###,Id.##,Par1.#### Par2.####
Error:Code execution error, Flag ###
External FAULT
Ext. Fault: Mains power
Ext. Fault: Battery
Ext. Fault: power supply
External power supply fault
EXTINGUISH device activation FAULT
FAULT in line to EXTINGUISH device
Fault on BMS−communication
FAULT port RS232
FAULT: re−alarm coll.ln, zone ###
FSD: door manually opened
fuse 'battery' BLOWN
fuse 'supply outp. 24V/0.5A' BLOWN
fuse 'supply outp. 24V/1A' BLOWN
HM/UE : feed back still active
HM:manually activated without fire
HM: no remote device feed back
HW/System error: Replace CPU board
HW error: Mismatch board ######
HW warn.: Mismatch board ######
INCONSISTENT user data
118
Building Technologies
Fire Safety & Security Products
Indicates a hardware problem.
% unpower system and re−power again
(if message comes on again replace main board K3X...)
Indicates a software problem.
% unpower system and re−power again
(if message comes on again replace main board K3X...)
Indicates a software problem.
% unpower system and re−power again
(if message comes on again replace main board K3X...)
External fault input activated.
% check connected devices
External fault mains power, battery, power supply.
% check device connected to 'K6' (Z3I1000 etc.)
Fault on power supply input 'K50'.
% check input 'K50' on K3X...
Message 'extinguishing actuated' without command
from fire alarm panel (only with VdS card).
% check extinguishing device
Open or short circuit in line to extinguishing device.
% check wiring
Communication fault on BMS communication.
% check connection from PC to control panel
Communication problem in serial ports.
% reset (if fault does not disappear, or if this is taking place
frequently % replace K3X...)
Zone is re−alarmed immediately (< 20sec) after reset.
(possibly defective detector).
% locate alarming detector check situation
FSD is released manually by switch 'S1' on VdS card K3L070
or unauthorized manipulation.
% check VdS card
Battery disconnected or fuse F3/F4 blown possibly due to
wrong polarity.
⇒ check battery and/or replace fuse % then reset
On power output 24V fuse 'F2' blown.
% check connected load and replace fuse
On power output 24V fuse 'F1'  blown.
% check connected load and replace fuse
After alarm reset ÜE still confirms alarm (only with VdS card).
% Check ÜE device
ÜE manually activated (only with VdS card).
% check ÜE device
ÜE activated but no confirmation (only with VdS card).
% check wiring or ÜE device
Indicates a hardware problem.
% unpower system and re−power again
(if message comes on again replace main board K3X...)
Actual configuration does not correspond with programmed
configuration.
% check wiring and configuration
Programmed user data and physical installation make do not
match.
% start function 'CHECK configuration' via menu
1)
1)
1)
1583_o_en_−−_7