Master board K3X020
Remote transmission alarm and fault
Horn 1 and 2
Stub lines 1/2 or Loop 1/2
LEDs 1 to 4
pluggable
connecting
terminals
LCD
Keyboard
Key-lock switch
K3M010
or
K3M020
or
K3M030
K3L070
or
K3G050
B3R080
and/or
K3L100
Pos.
Description
H1/H2
LED "EARTH FAULT" 0V / 24V" earth fault to 0V or 24V
1
2
H8
LED "5V LOW" 5V supply voltage too low
3
H7
LED "5V POWER" 5V supply voltage available
H5/H6
LED "CH2 RXD" (receive) "TXD" (transmit) of RS232-2
4
5
H3/H4
LED "CH1 RXD" (receive) "TXD" (transmit) of RS232-1
6
H9
LED "CP" current pulse detector communication
S1
Momentary switch to restart the system
7
8
S2
Momentary switch to "DELETE alarm counter"
9
ST8/ST9/ST10
Jumper to select battery make (brand) see page 21
10
ST1
Jumper / removed = watchdog inactive
ST2
Jumper / removed = earth leak detection inactive
11
Jumper / set to top = NTC disabled → no temperature compensation
12
ST3
ST7
Jumper / removed = buzzer disabled
13
Supply mode:
external 24V
Mains + external 24V
14
ST11–ST14
1)
Mains without battery
Mains + Battery (K9)
MP1/MP2
Pins to pickup 5V for RS232/LON converter card K3I080
15
1) jumper not to change while system is in operation
3.4
Quick installation check
Building Technologies
Fire Safety & Security Products
Inputs
Alarm contact
11
10
8
7
13
EPROM EP2 (2MB or 4MB)
(K50):
DC
(K50):
DC
Function 'automatic configuration'
mains fuses
mains 115/230V
AC
24V supply
Outputs
14
9
6
2
12
5
4
sensor (NTC) for temperature
1
compensation system voltage
RS232-2 application see page 114
RS232-1 application see page 114
EPROM EP1(4MB)
Jumper ST11 inserted
Jumper ST12 inserted
Jumper ST13 inserted
Jumper ST14 inserted
630mA/T
→ 1,25A/T)
(115V
AC
100VA
3
15
Battery
Potentiometer to adjust battery charging
voltage on 'K9'
Normal state / position
not lit
not lit
lit
pulsating during communication
pulsating during communication
pulsating
set according battery make
ST9 default (at factory)
inserted
inserted
inserted to 'bottom' (at factory)
see page 106
inserted
default (at factory)
53
1583_o_en_−−_3