Siemens Synova FC330A Manual page 46

Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

2.21
Connecting line extension card K3M010
mounting see page 25, 26
Jumper X1 – X4
Pos. 'left' = detector series SynoLINE600 (default)
Pos. 'right' = detector series SynoLINE300
! only available with index 'a' onwards
! jumper must be either on pos. 'left' or 'right' (do not remove)
Terminal blocks K12 to K17 are pluggable
K3M010
LINE
Conventional line 5
Conventional line 6
Conventional line 7
Conventional line 8
BELL
Terminal block
Horn 3
monitored
Horn 4
monitored
CONTROL
RL3
Alarm contact 3
(active until reset)
RL4
Alarm contact 4
(active until reset)
OUTPUT
Programmable control output 9
Programmable control output 10
Programmable control output 11
Programmable control output 12
42
Building Technologies
Fire Safety & Security Products
(X1 = line 1, X2 = line 2 etc.)
Terminal block K12
+
1
2
+
3
4
+
5
6
+
7
8
K13
+
F1
1
24V
J
0,5A/F
2
F2
+
3
J
24V
0,5A/F
4
Terminal block K14
1
NO
2
NC
3
C
4
NO
5
NC
6
C
Terminal block K17
J
1
J
2
J
3
J
4
lines 5 to 8
connection to
K3X020 connector A
4 EOL20
4 spacer bolts L=25
max. 32 detectors
max. 32 detectors
max.0,5A
max.0,5A
max. 30V / 1A
max. 30V / 1A
A1
A2

connect to K8 / K3X020
outputs
alarm contact
horns 3 and 4
2 resistors 12kW ½W
J
total current available for all control outputs
and 24V-power output is 1,5A
Details detectors see
EOL20
manual FD-M
Detail SynoLINE600
see page 33 / 110
EOL20
12kW ½W
Detail see page 111
12kW ½W
Detail see page 112
Z3B171
14
12
10A / 250V
AC
11
5V supply
voltage
available
Example
air condition-
ing control
2nd floor
1583_o_en_−−_2
08.2005