Siemens Synova FC330A Manual page 104

Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

5.20
Programming input signals
CONFIGURATION:
1. system data
(4.4.1)
2. collective line
3. password
4. addressable line
5. SWE330A
6. LON devices
7. serial ports
8. K6 inputs
Display
K6 inputs:
1: ######
(4.4.1.8)
2: ######
3: ######
>Sel. input
4: ######
Possible options
Not used
to toggle between manned/unmanned
to activate alarm horns
to acknowledge system
to reset system
to initiate lamp test
to signal FAULT from external
to disable remote transmission (alarm+fault)
to signal mains fault from external
to signal battery fault from external
to signal power fault from external
to initiate ALARM from external
to disable 'fire controls' (see page 62)
100
Building Technologies
Fire Safety & Security Products
ê
to define basic functions and alarm organization
ê
to define the conventional lines (only if K3M010 or K3M020 is equipped)
ê
to overwrite the 4 basic passwords
ê
to define the addressable lines / logical detector zones and conTrol zones
ê
for data transfer FC330A
ê
to define the floor repeater and control panels
ê
to define the application on the serial ports
ê
to define programmable inputs on K3X0x0 / K6
None
External CAC
Evacuation
ACKNOWLEDGE
RESET
lamp test
external FAULT
DISABLE RT
ext. Fault mains
ext. Fault batt
ext. Fault power
External Alarm
DISABLE fire ctrl.
Ö
PC (see page 70)
1583_o_en_−−_5
08.2005