2.26
Connecting LED driver card K3L100
mounting see page 25...27
K3L100 can be used
simultaneously with
B3R080 or by it self
K3L100
OUTPUT
Pluggable terminal block K1
LED outputs 1 – 16
5V / max. 15mA
short circuit proof
EMC protected
Pluggable terminal block K2
LED outputs 17 – 32
5V / max. 15mA
short circuit proof
EMC protected
INPUT / OUTPUT
Pluggable terminal block
Input lamp test
Input buzzer OFF
Output LED 'ON'
5V/max. 15mA
Output buzzer
5V/max. 15mA
Building Technologies
Fire Safety & Security Products
to connector C
to B3R080
if required
+
+
1
2
3
4
LED 1
5
6
7
8
+
+
9
10
11
12
13
14
15
16
LED 16
+
+
17
18
19
20
LED 17
21
22
23
24
+
+
25
26
27
28
29
30
31
32
LED 32
K3
7
6
5
4
+
3
2
+
1
LED 17-32
in-/outputs
LED 1-16
6 Pan-head screws
6 washers
max. line length
LED 1...32
S to be allocated to one or several detector
ZONE(S)
S common allocation with B3R080
(see setting user applications)
S only activated on alarm
S no serial resistor for external LEDs needed
S onboard 5V converter
activates all outputs as long as input is activated
turns off output buzzer
active if 5V power inside K3L100 is ON
active as long as LED 1.....32 is active or until
input 'buzzer OFF' is activated
2 cable holders
6 spacer bolts L=32
0,8mm O = ......400m
0,6mm O = ......200m
47
1583_o_en_−−_2
08.2005

Hide quick links: