Siemens Synova FC330A Manual page 112

Fire detection system
Hide thumbs Also See for Synova FC330A:
Table of Contents

Advertisement

Local alarm
(alarm stage 1)
Local alarm
Confirm message
Investigate fire location and decide
− emergency
− minor incident
Remote alarm
Alarm stage 2
Local alarm
Alarm initiated by detectors during 'V1' or 'V2' is running
Remote alarm
Alarm initiating the remote transmission
− initiated in mode 'manned' after 'V1' or 'V2' has expired
− immediately initiated by manual call point
− immediately initiated by any alarm during mode 'unmanned'
Alarm horn
Activated either
− on 'remote alarm' only or on 'local alarm' + 'remote alarm' é default = remote alarm
− can be silenced via function key 'acknowledge'
The sound mode can be programmed either
− as 'continuous' or 'pulsating' signal
Special function 'EXTRA TIME'
Allows to set the system to 'manned' after the automatic switchover has taken place for the preset time of
max. 9:00h
Zones excluded from alarm organization
Zones that report 'non fire events' can be excluded from the alarm organization
− Zones not initiating 'remote transmission' (RT)
− Zones not initiating 'alarm horn'
108
Building Technologies
Fire Safety & Security Products
F
(also called 'alarm stage 1')
(also called 'alarm stage 2')
(acoustic alarm devices)
Mode:
'manned'
V1
Ackn.
no
acknowledged
?
yes
V2
Reset
reset
?
no
é only applies for zone ty
or MULTI−LOC
é default = pulsating
Programming steps see page 74
Programming steps see page 85
'manned'
'unmanned'
or
'unmanned'
F
1583_o_en_−−_6
08.2005