2.16
Connecting of conventional SynoLINE300 devices
Note: for technical details see page 110
to run SynoLINE300 set jumper on the line extension card K3M010/020 accordingly see page 42, 43
−> list order and type of all devices (field device list)
Smoke/heat detectors
Base SO320
OH320C
+
+
+
+
line
micro terminals
+
AI320
AI322
max. 2 response indicators
Signal contact
+
alarm
contact
Resistor 470Ω / 1,5W or Z-Diode 5,6V / 1,5W
Manual call points
Resistor 1.2kΩ
+
line
+
MT320C
Building Technologies
Fire Safety & Security Products
Base SO320
HI32xC
+
+
+
+
Response
indicator
AI322
EOL20
Resistor 1.2kΩ
+
MT320C
Base SO320
Response
indicator
AI320
S terminate each detector line with EOL20
S do not mix automatic detectors with
manual call points
S max. 32 smoke/heat detectors per line
EOL20
Resistor 1.2kΩ
+
MT320C
(current limited)
OP320C
+
+
+
EOL20
+
AI320
AI322
MT320C