Figure 11-3. Settings Explorer, Alarm Configuration, Horn Configuration Screen
Sender Failure
To configure sender failure alarms using BESTCOMSPlus, open the Sender Fail screen (Figure 11-4).
This screen is found in the Settings Explorer under the Alarm Configuration category. If using the front
panel, navigate to Settings > Alarm Configuration > Sender Fail.
Coolant temperature, oil pressure, fuel level, and voltage sensing sender failure settings consist of an
alarm configuration setting and an activation delay. The alarm configuration setting allows selection of the
type of alarm to be annunciated when a sender fail condition exists. None, Alarm, and Pre-alarm can be
selected. The selected alarm type is triggered when a sender failure exists for the duration of the
activation time delay.
Speed sender failure settings consist of a single activation delay. An alarm is triggered when a speed
sender failure exists for the duration of the activation time delay.
Figure 11-4. Settings Explorer, Alarm Configuration, Sender Fail Screen
Alarm Configuration
DGC-2020ES