Basler DGC-2020ES Configuration Instruction Manual page 118

Digital genset controller
Hide thumbs Also See for DGC-2020ES:
Table of Contents

Advertisement

13-18
Name
Service Tool
A manual or forced regeneration is in progress and
Forced
was initiated from a manufacturer's service tool. This
Regenerate
indication is received from the engine ECU over
J1939 CAN Bus as SPN 4175 Diesel Particulate
Filter Active Regeneration Forced Status or SPN
6934 SCR System Cleaning Forced Status. When
the value is 2, a Service Tool Forced Regenerate
pre-alarm is annunciated.
Switch Forced
A manual or forced regeneration is in progress and
Regenerate
was initiated from a manual regeneration switch.
This indication is received from the engine ECU over
J1939 CAN Bus as SPN 4175 Diesel Particulate
Filter Active Regeneration Forced Status or SPN
6934 SCR System Cleaning Forced Status. When
the value is 1, a Switch Forced Regenerate pre-
alarm is annunciated.
Torque Limit
True while the engine is running in a reduced torque
mode due to exhaust system issues such as Low
DEF, Purge Required, Exhaust System Error, etc.
This reflects the status of the exhaust system
Torque Limit lamp, which is communicated from the
Engine ECU to the DGC-2020ES via J1939 CAN
Bus communications.
Torque Limit
True while the engine is running in a severely
Severe
reduced torque mode due to exhaust system issues
such as Low DEF, Purge Required, Exhaust System
Error, etc. This reflects the status of the exhaust
system Torque Limit lamp, which is communicated
from the Engine ECU to the DGC-2020ES via J1939
CAN Bus communications.
Voltage
True when the Voltage Sensing Fail is configured as
Sensing Fail
a pre-alarm and the activation delay has expired.
Weak Battery
True when the Weak Battery Voltage Pre-Alarm
settings have been exceeded.
Senders
Coolant Temp
True when the Coolant Temp Sender Fail is
Sender Fail
configured as either a pre-alarm or alarm and the
activation delay has expired.
Fuel Level
True when the Fuel Level Sender Fail is configured
Sender Fail
as either a pre-alarm or alarm and the activation
delay has expired.
Oil Pressure
True when the Oil Pressure Sender Fail is
Sender Fail
configured as either a pre-alarm or alarm and the
activation delay has expired.
Speed Sender
True when the Speed Sender Fail activation delay
Fail
has expired.
Voltage
True when the Voltage Sensing Fail is configured as
Sensing Fail
either a pre-alarm or alarm and the activation delay
has expired.
BESTlogic™Plus
Description
9469200995
Symbol
DGC-2020ES