DGC-2020ES
Description
This element is used to connect the breaker open and
close output signals from the DGC-2020ES to physical
output contacts to open and close the mains breaker and
map breaker status feedback to a contact input. In
addition, contact inputs can be mapped to allow switches
to be implemented to manually initiate breaker open and
close requests.
This element is only available when the Mains Breaker
Hardware in configured on the Breaker Hardware screen
via the Breaker Management tree branch.
Inputs
Status: This input allows a contact input to be mapped
that will provide breaker status feedback to the DGC-
2020ES. When the contact input is closed, the breaker is
indicated to be closed. When the contact input is open,
the breaker is indicated to be open.
Open: This input allows a contact input to be mapped that
can be used to initiate a manual breaker open request.
When this input is pulsed closed while the DGC-2020ES
is in RUN or AUTO mode, the breaker will open.
Close: This input allows a contact input to be mapped
that can be used to initiate a manual breaker close
request. When this input is pulsed, the mains is stable,
and both breakers are open, a close request will be
initiated.
Outputs
The outputs must be mapped to the contact outputs of
the DGC-2020ES that will be used to drive the breaker.
Open: This output is pulsed true (closes the output
contact it is mapped to) when the DGC-2020ES is
providing a signal to the breaker to open. It will be a pulse
if the Breaker Output Contact Type is set to Pulse on the
Breaker Hardware screen under Breaker Management in
the Settings Explorer, and the length is determined by the
Open Pulse Time. It will be a constant output if the Mains
Breaker Hardware Contact Type is set to continuous.
Note the pulse time must be set long enough for the
breaker to actually open before the pulse is removed.
Close: This output is pulsed true (closes the output
contact it is mapped to) when the DGC-2020ES is
providing a signal to the breaker to close. It will be a
pulse if the Breaker Output Contact Type is set to Pulse
on the Breaker Hardware screen under Breaker
Management in the Settings Explorer, and the length is
determined by the Open Pulse Time. It will be a constant
output if the Mains Breaker Hardware Contact Type is set
to continuous. Note the pulse time must be set long
enough for the breaker to actually open before the pulse
is removed.
When this logic element is true, Cylinder Cutout Disable 1
and Cylinder Cutout Disable 2 are both sent to the engine
ECU with true status. When this logic element is false,
Cylinder Cutout Disable 1 and Cylinder Cutout Disable 2
are sent to the engine ECU with states set by the values
programmed for the Cylinder Cutout Disable 1 and
Cylinder Cutout Disable 2 DGC-2020ES settings which
are configured on the ECU Setup screen in
BESTCOMSPlus.