4-12
Remote Display Panel (optional)
Applications that require remote annunciation can use Basler Electric's Remote Display Panel. This
device provides remote indication of many pre-alarm and alarm conditions.
Remote Display Panel connections are made at 10 (RDP TxD–), 11 (RDP TxD+), 17 (BATT–), and 18
(BATT+).
The following pre-alarm conditions are indicated by LEDs on the Remote Display Panel:
High coolant temperature
Low coolant temperature
Low oil pressure
Low fuel level∗
Weak battery
Battery overvoltage†
Battery charger failure∗†
The following alarm conditions are indicated by LEDs and an audible alarm on the Remote Display Panel:
Low coolant level∗
High coolant temperature
Low oil pressure
Overcrank
Overspeed
Emergency stop activated
Fuel leak/Sender failure∗†
Sender failure†
∗ This can be configured in the DGC-2020ES as None, Alarm, or Pre-alarm. See the Contact Inputs