13-22
Name
AUTOBRKOP-
INHIBIT
CONFELMNTX
(X = 1 to 8)
COOLSTOPREQ
BESTlogic™Plus
Description
Automatic breaker operation is inhibited when the Set
input is true.
Configurable elements (CONFELMNT1-8) are connected
to the logic scheme as outputs. These elements are
configurable in BESTCOMSPlus under Programmable
Outputs, Configurable Elements. The user can assign a
string of up to 16 characters, configure whether the
element should generate an alarm or pre-alarm. If used
for alarm or pre-alarm, the user's text is what will appear
in the alarm or pre-alarm annunciation and in the DGC-
2020ES event log.
RUN Mode
If the unit is in RUN mode when the Cool Stop Request is
received, the unit will unload, open its breaker, and go
into a cooldown cycle. While in the cooldown cycle, the
unit will display "COOL & STOP REQ" in addition to
displaying the cooldown timer. After the cooldown timer
expires, the unit will go to OFF mode. The Cool Stop
Request must be removed before the unit can be run
again.
If the Cool Stop Request is removed during the cooldown
process, the unit will remain running. Furthermore, if a
condition occurs that normally causes the unit to close its
breaker in RUN mode, the unit will close its breaker and
reload.
AUTO Mode
If the unit is in AUTO mode when the Cool Stop Request
is received, all conditions that would normally cause the
unit to run in AUTO mode are cleared. Since all
conditions that cause the unit to run have been removed,
the unit goes into a cooldown cycle. While in the
cooldown cycle, the unit will display "COOL & STOP
REQ" in addition to displaying the cooldown timer. After
the cooldown timer expires, the unit will shut down,
remaining in AUTO. The Cool Stop Request must be
removed before the unit can be run again.
If the Cool Stop Request is removed during the cooldown
process and some condition that would normally cause
the unit to run in AUTO mode is true, the unit will remain
running. Furthermore, if a condition occurs that normally
causes the unit to close its breaker, the unit will close its
breaker and reload.