9469200995
Name
Generator
True when the 81 Under element is configured as an
Protection
alarm and has tripped.
81 Under
Global Alarm
True when one or more alarms are set.
Global Sender
True when one or more of the Sender Fails are
Fail
configured as alarms and are true.
Hi Coolant
True when the High Coolant Temp Alarm settings
Temp
have been exceeded.
Isuzu DEF Low
True when an Isuzu engine ECU has detected low
Refill DEF
DEF level and indicated the DEF symbol should be
displayed, and the Isuzu No Power Lamp is active
indicating that the engine has been shut down.
Low Coolant
True when the Low Coolant Level function is
Level
configured as an alarm and the activation delay has
expired. In addition, true when CAN Bus is enabled
and the Low Coolant Level Alarm threshold has
been exceeded.
Low Fuel Level
True when the Low Fuel Level Alarm settings have
been exceeded.
Low Oil
True when the Low Oil Pressure Alarm settings
Pressure
have been exceeded.
Mains Fail
True when a mains fail transfer fail pre-alarm
Transfer Failed
occurs. The pre-alarm occurs when the DGC-
2020ES is configured for mains fail transfers, but
has not transferred to the generator from the utility
before the Mains Fail Max Transfer Time has
expired. It remains true until the pre-alarm is cleared
by pressing the Reset button on the front panel.
MTU Combined
This is an indication from the MTU Engine ECU that
Red
a Red Alarm has occurred. If any Red Alarm occurs,
a Combined Red Alarm occurs.
Oil Pressure
True when the Oil Pressure Sender Fail is
Sender Fail
configured as an alarm and the activation delay has
expired.
Overcrank
True when an Overcrank condition exists.
Overspeed
True when the Overspeed Alarm settings have been
exceeded.
Speed Sender
True when the Speed Sender Fail activation delay
Fail
has expired.
Unexpected
True when the metered engine speed (RPM)
Shutdown
unexpectedly drops to 0 while the engine is running.
Alarm
Voltage
True when the Voltage Sensing Fail is configured as
Sensing Fail
an alarm and the activation delay has expired.
DGC-2020ES
Description
13-11
Symbol