Basler DGC-2020ES Configuration Instruction Manual page 110

Digital genset controller
Hide thumbs Also See for DGC-2020ES:
Table of Contents

Advertisement

13-10
Name
Coolant Level
True when a low coolant level error status code is
Sender Fail
received from the ECU. CAN Bus must be enabled.
True when the Coolant Temp Sender Fail is
Coolant Temp
configured as an alarm and the activation delay has
Sender Fail
expired.
DEF Severe
This alarm indicates the highest level of inducement
Inducement
not to operate the engine due to low or poor quality
Diesel Exhaust Fluid (DEF), or a malfunction in the
Exhaust After Treatment System (EATS). The
engine may operate in a reduced power mode, or for
a limited time, or may be prevented from starting by
the ECU until the problem is corrected. A service
tool may be required to restart the engine.
Diagnostic
True when a Diagnostic Trouble Code alarm exists.
Trouble Code
ECU Comm
True when communication to ECU has been lost.
Loss
ECU Shutdown
True when ECU has shut down the engine.
Emergency
True when the Emergency Stop button has been
Stop
pressed.
Exhaust System
This alarm annunciates when the DEF Inducement
Error
Level is greater than or equal to 3, the Isuzu
Exhaust System lamp is on, and the Isuzu No Power
lamp is on. The Exhaust System Error alarm
appears in conjunction with a DEF Severe
Inducement alarm to indicate why the machine has
entered the severe inducement state due to SCR
system malfunction.
Fuel Leak
True when the Fuel Leak Detect function is
configured as an alarm and the activation delay has
expired.
Fuel Level
True when the Fuel Level Sender Fail is configured
Sender Fail
as an alarm and the activation delay has expired.
True when the 27 element is configured as an alarm
Generator
and has tripped.
Protection
27
True when the 59 element is configured as an alarm
Generator
and has tripped.
Protection
59
True when the 47 element is configured as an alarm
Generator
Protection
and has tripped.
47
True when the 50 element is configured as an alarm
Generator
and has tripped.
Protection
50
True when the 81 Over element is configured as an
Generator
alarm and has tripped.
Protection
81 Over
BESTlogic™Plus
Description
9469200995
Symbol
DGC-2020ES