DGC-2020ES
Description
RUN Mode
If the unit is in RUN mode when the Cool Down Request
is received, the unit is forced to unload and open its
breaker and then go into a cooldown cycle. While in the
cool down cycle, the unit will display "COOLDOWN REQ"
in addition to displaying the cooldown timer. After the
cooldown timer expires, the unit will remain running in
RUN mode. The Cool Down Request must be removed
before the breaker can be closed again; this element
blocks breaker closures.
If the Cool Down Request is removed during the cool
down process, the unit will remain running in RUN mode.
Furthermore, if a condition occurs that normally causes
the unit to close its breaker in RUN mode, the unit will
close its breaker and reload.
AUTO Mode
If the unit is in AUTO mode and the Cool Down Request
is received, the unit is forced to unload and open its
breaker and go into a cooldown cycle. While in the
cooldown cycle, the unit will display "COOLDOWN REQ"
in addition to displaying the cooldown timer. After the cool
down timer expires, the unit will remain running in AUTO
mode, unless there are no conditions that cause the unit
to run in AUTO mode, in which case it will shut down and
remain in AUTO mode. The Cool Down Request must be
removed before the breaker can be closed again; this
element blocks breaker closures.
If the Cool Down Request is removed during the cool
down process and some condition that would normally
cause the unit to run in AUTO mode is true, the unit will
remain running in AUTO mode. Furthermore, if a
condition occurs that normally causes the unit to close its
breaker, the unit will close its breaker and reload.
When true, cylinder cutout is enabled. When false,
cylinder cutout is disabled when any of the following are
true:
Synchronization is in progress.
The machine is operating with the generator
breaker closed.
The Cylinder Cutout Disable setting is true.
The Cylinder Cutout Disable logic element is
true.
Diesel Particulate Filter Regeneration is forced manually
when the Set input is true.
Diesel Particulate Filter Regeneration is inhibited when
the Set input is true.
When true, a Key On signal is applied to the ECU and
CAN Bus data is updated any time except during the
Disconnecting state.
13-23