Basler DGC-2020ES Configuration Instruction Manual page 108

Digital genset controller
Hide thumbs Also See for DGC-2020ES:
Table of Contents

Advertisement

13-8
Name
Status Input
True when the DGC-2020ES is configured for mains
Mains Fail
fail transfers and has successfully transferred to the
Transfer
generator from the utility. It remains true until the
Complete
utility power is deemed good and the DGC-2020ES
transfers the load back to utility power.
Status Input
True when the Mains Fail Transfer Functionality is
not enabled or when the DGC-2020ES is operating
Mains Fail
in the Off or Run modes or in the alarm state.
Transfer
Disabled
True when mains fail transfer function detects the
Status Input
load is powered from the generator bus.
Mains Fail
Transfer
Power from
Gens
True when mains fail transfer function detects the
Status Input
load is powered from the mains bus.
Mains Fail
Transfer
Power from
Mains
Status Input
True when mains fail transfer return delay timer is
actively counting.
Mains Fail
Transfer
Return Timer
Active
True when the mains fail transfer delay timer is
Status Input
actively counting.
Mains Fail
Transfer
Transfer Timer
Active
True when mains fail transfer is transferring load to
Status Input
the generator bus.
Mains Fail
Transfer
Transferring to
Gens
Status Input
True when mains fail transfer is transferring load to
the mains bus.
Mains Fail
Transfer
Transferring to
Mains
True when the DGC-2020ES is in Off Mode or the
Status Input
Off Mode
Off Mode logic element is true.
Status Input
True when the DGC-2020ES is in Off Mode and
Off Mode
cooling down.
Cooldown
Status Input
True when the open transition delay is actively
counting.
Open Transition
Delay
True while in the Pre Start state.
Status Input
Pre Start
Condition in
Effect
BESTlogic™Plus
Description
9469200995
Symbol
DGC-2020ES