Figure 5-4. Settings Explorer, System Parameters, Crank Settings Screen
Automatic Restart
When enabled, the Automatic Restart clears all alarms automatically if the DGC-2020ES shuts down due
to an alarm condition. An attempt to restart the engine is made, after a predetermined time delay, if the
ATS contact input is closed. If an ATS contact is not present, the unit remains in the READY state with
alarms cleared. A restart is not attempted if a low fuel alarm or emergency stop is present. The number of
restart attempts is programmable. Automatic restart attempts are recorded in the event log.
The Auto Restart Interval setting accepts values from 0.5 to 30, in increments of 0.5 minutes. The Auto
Restart Attempts setting accepts values from 1 to 10, in increments of 1.
The Automatic Restart screen is found in the BESTCOMSPlus Settings Explorer under the System
Parameters category. If using the front panel, navigate to Settings > System Parameters > Automatic
Restart.
The BESTCOMSPlus Automatic Restart screen is illustrated in Figure 5-5.
Figure 5-5. Settings Explorer, System Parameters, Automatic Restart Screen
Exercise Timer
The exercise timer function starts and runs the genset at specified intervals. Exercise timer settings are
described in the following paragraphs.