Basler DGC-2020ES Configuration Instruction Manual page 112

Digital genset controller
Hide thumbs Also See for DGC-2020ES:
Table of Contents

Advertisement

13-12
Name
Pre-Alarms
Battery Charger
True when the Battery Charger Fail function is
Fail
configured as a pre-alarm and the activation delay
has expired.
True when the ac power to the battery charger is off.
Battery Charger
(Battery Charger 1 shown.)
AC Off
Battery Charger
True when the battery charger has detected that the
battery has failed. (Battery Charger 1 shown.)
Battery Failure
True when the battery charger has detected a J1939
Battery Charger
communications failure. (Battery Charger 1 shown.)
Comms Fail
Battery Charger
True when the battery charger has failed. (Battery
Charger 1 shown.)
Fail
True when the battery charger output voltage is too
Battery Charger
high. (Battery Charger 1 shown.)
High Output
Volts
True when the battery charger has detected invalid
Battery Charger
settings. (Battery Charger 1 shown.)
Invalid Settings
Battery Charger
True when the battery charger has detected that the
voltage while the engine is cranking has dipped too
Low Cranking
low. (Battery Charger 1 shown.)
Volts
True when the battery charger output voltage is too
Battery Charger
low. (Battery Charger 1 shown.)
Low Output
Volts
True when the battery charger has detected one or
Battery Charger
more charging output stages in a charger with
Single Unit Fail
multiple charging output stages has failed. (Battery
Charger 1 shown.)
Battery Charger
True when the battery charger temperature is
beyond the thermal limit. (Battery Charger 1 shown.)
Thermal Limit
Battery
True when the Battery Overvoltage pre-alarm
Overvoltage
threshold has been exceeded.
Cannot Regen -
True when the regeneration interlock has failed on a
Interlock Fail
Yanmar ECU. Manual regeneration is blocked.
Cannot Regen -
True when the coolant temp is low on a Yanmar
Low Coolant
ECU. Manual regeneration is blocked.
Temp
Cannot Regen -
True when 50 hours has not elapsed since last
Not 50 Hours
regeneration on a Yanmar ECU. Manual
Since Last
regeneration is blocked.
Regen
Checksum
True when some of the user settings or firmware
code has been corrupted. Refer to the Reporting
Failure
and Alarms chapter for more details.
BESTlogic™Plus
Description
9469200995
Symbol
DGC-2020ES

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents