Database Objects
Object
Mapping
Button configuration: XY where X is the number of top row
AV507
buttons and Y is the number of bottom row buttons
AV508
Button Overlay number as defined in the product Catalog
Sheet and the Overlay Selection Guide. 0 =
custom/unknown
Motion Sensitivity 0-100%
AV509
CO2ManualCalibration
AV511
Enable or disable calibration mode. Auto calibration can
be enabled by setting AV511 to 0. Manual calibration
mode can be enabled by setting AV511 object to 1 in
manual mode. Manual calibration mode is enabled by
default. (AV511 = 1)
Value changes via GCL do not update sensor mode. The
firmware reads the value every 10 seconds and ignores
any other value besides 0 or 1 assigned to AV511.
The CO2 calibration command only works for an scd30
type sensor. This object is auto-created in the database if
the model name includes the CO2 sensor option.
See the information in the
eZNxxx CO2 Sensor
Page 66 of 126
Calibrate an enteliZONE
section.
eZNT-Wi Programmable Wi-Fi Thermostat Application Guide
R/W
R
R
R/W
R/W
Edition 1.4