On-Screen Menu Configuration
Menu
Item
Options
Delta
LCD
Font
CLb
AP
oFF
on
Page 58 of 126
Default
Description
This item normally shows the real time raw
value of the CO2 sensor.
When the previous Clb item is initially set to
Yes (manual calibration mode), this field
accepts up to four digits representing the
ppm value of the calibration CO2 gas. The
ppm value must be between 400-2000 or a
Value Out of Range error occurs when the
firmware tries to write it.
See the procedures in the
enteliZONE eZNxxx CO2 Sensor
Turns the Access Point Host (AP) mode on or
oFF. In AP mode, the internal radio on the
eZNT-Wi/ eZNTW unit is used. AP mode
provides easy access to the configuration
webpage for a specific unit during initial
configuration.
If the AP Host mode is on for 30 minutes
without activity, it switches oFF and the
eZNT-Wi/ eZNTW communicates only in
Station Client mode.
eZNT-Wi Programmable Wi-Fi Thermostat Application Guide
Calibrate an
topic.