Delta enteliZONE eZNT-Wi Series Application Manual page 57

Table of Contents

Advertisement

Menu
Item
Options
Delta
LCD
Font
0-100%
Occ
AUTO
CLb
Yes
eZNT-Wi Programmable Wi-Fi Thermostat Application Guide
Edition 1.4
Default
Description
Sets motion/ occupancy sensitivity. The
50%
default is 50% but may need adjustment
based on the room size/layout.
0% is least sensitive but will likely miss
motion at full range, while 100% is most
sensitive but will likely generate false
detections.
Variable AV509 provides another way to
configure this value.
This menu item is only available if a motion
sensor is installed on the PCB.
Yes
If CLb set to Yes, the factory default manual
(manual
calibration mode is enabled. In most cases,
calibration)
manual calibration mode is the preferred
mode of operation. The following additional
menu CLb item initially shows the current
CO2 value.
If set to AUTO, CLb (auto calibration mode)
is set to Auto CO2 sensor calibration mode.
Auto calibration looks for periodic minimum
CO2 readings in buildings that come down to
the outdoor ambient CO2 level typically
during nightly unoccupied periods.
See the procedures in the
enteliZONE eZNxxx CO2 Sensor
Calibrate an
topic.
Page 57 of 126