4. WOW6432Node|DeltaControls|3.40|Commander|ForceSubscribeNetwork
5. Set the value of the new registry key to 1.
6. Restart OWS.
7. From OWS login dialog, select the enteliZONE thermostat Virtual Com Port
(e.g. COM3) as a COM Port through the OWS Logon dialog. From the Advanced
– Connect Using dropdown options, select Serial: BACnet MS/TP.

Access an enteliZONE Thermostat Using its USB Service Port

You can use an ORCAview or enteliWEB 4.8+ BACnet front end to access the objects
on the thermostat and also the rest of the BACnet network.
With ORCAview, you may need to add a registry entry. See the
entry for USB Service Port access
With enteliWEB 4.14, the Add Connection dialog now shows the available COM Port
choices and you no longer have to type in the COM port number into the field. With
enteliWEB 4.8+, you need to set up MS/TP communications through the virtual port.
For enteliWEB 4.8 to 4.13, the virtual port does not show in the dropdown and you
must manually add the correct port number (e.g. Com4).

Use enteliWEB with eZNS and eZNT

The enteliWEB 4.14 release supports a wired connection to an enteliZONE product
using the micro USB port on the enteliZONE thermostat. This feature provides
access to the objects in the products using a connection to the micro USB port. Your
laptop/ PC has enteliWEB 4.14+ and has a virtual COM driver installed. You can also
eZNT-Wi Programmable Wi-Fi Thermostat Application Guide
Edition 1.4
procedure.