S-Singel Stage Controller Object (Class Id 51) - VAT 615 Series Installation, Operating, & Maintenance Instructions

Dn 40 (i.d. 1 1/2”), devicenet, butterfly control & isolation valve with extended control range, with devicenet interface
Table of Contents

Advertisement

4.12 S-Singel Stage Controller Object (Class ID 51)

Command
CONTROL MODE
CONTROL
SETPOINT
PRESSURE
SENSOR SELECTION
VALVE SPEED
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
Installation, Operating & Maintenance Instructions
Series 615 DN 40 (I.D. 1½"), DeviceNet
Service Code
Class ID
Set
16
51
Get
14
Y:
0
control (pressure resp. position control)
1
close valve (valve will close)
2
open valve (valve will open)
3
hold (stops the valve at the current position)
4
safe state (valve will close)
This command preselects / returns the control mode for pressure resp. position control. By
means of instance ID either pressure or position must be addressed.
Set
16
51
Get
14
position setpoint according to selected DATA TYPE, 0 (closed) ... 10'000 (open)
Y:
or
Y:
pressure setpoint according to selected DATA TYPE,
nominal pressure range is 0 ... 10'000 (sensor full scale) but it may be scaled,
refer also to command GAIN for details.
This command transfers/reads the position/pressure setpoint to/from the valve.
Get
14
51
This command returns the actual pressure according to selected DATA TYPE. Nominal
pressure range is 0 ... 10'000 (sensor full scale) but it may be scaled. Refer also to
command GAIN and picture on the following page for details.
Set
16
51
Get
14
X:
1
Sensor 1
2
Sensor 2
3
Auto
This command selects/returns the source of process variable for process control function.
Set
16
51
Get
14
valve speed, 1 ... 1000 (1 = min. speed, 1000 = max. speed),
X:
This command selects/returns the actuating speed for the valve plate. Data type is unsigned
integer. Speed selection is effective for pressure control and position control. Open valve
and close valve are always done with max. speed.
Note: Refer to «Valve speed adjustment» for details.
Instance ID
Attribute ID
Description
1 (pressure)
5
2 (position)
1 (pressure)
6
2 (position)
1
7
1
96
2
101
Service
Service
data length
data field
(number of bytes)
Y
1
Y
2 int
4 float
2 int
4 float
X
1
X
2
603476EA
70/102
2013-07-25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

61532-keaq-0001

Table of Contents