3.11.1.4
Valve speed adjustment
Valve speed effects:
Response time
Default value is 1000. Adjustment range is from 1 to 1000.
This parameter effects valve plate actuating speed.
Speed adjustment is effective for PRESSURE CONTROL and POSITION CONTROL.
Note: Normally best pressure control response is achieved with max. valve speed. In particular applications it may be of
advantage to have a slower valve response.
Note: OPEN and CLOSE are always done with max. speed.
Adjustment procedure:
1.
Use optimal gain factor, sensor delay time and setpoint ramp according to preceding tuning steps.
2.
Open valve.
3.
Control a typical pressure / flow situation.
4.
Repeat from step 2 with slower valve speed until required response is achieved.
Local
('Control View', 'Control Performance Analyzer' or
Go to 'Setup / Control Parameter' menu. Select valve
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
Installation, Operating & Maintenance Instructions
Series 615 DN 40 (I.D. 1½"), DeviceNet
operation:
'Service Box 2')
speed.
Remote
(Refer to chapter «S-Singel Stage Controller Object»
for details)
Send PID CONTROLLER VALVE SPEED
operation:
603476EA
45/102
2013-07-25