Cisco ONS 15454 Series Procedure Manual page 164

Dwdm
Hide thumbs Also See for ONS 15454 Series:
Table of Contents

Advertisement

Required Tools and Equipment (ETSI)
Step 1
Open the latches/ejectors of the first TCC2/TCC2P/TCC3 card that you will install.
Use the latches/ejectors to firmly slide the card along the guide rails until the card plugs into the
Step 2
receptacle at the back of the slot (Slot 7 or 11).
Note
Verify that the card is inserted correctly and close the latches/ejectors on the card.
Step 3
Note
If you insert a card into a slot provisioned for a different card, all LEDs turn off.
As needed, go to Step
Step 4
the TCC3 card go to Step c.
a.
For the TCC2 card:
Note
Note
Note
Note
Cisco ONS 15454 DWDM Procedure Guide, Release 9.2
1-76
In
Step
4, you will be instructed to watch the LED activity (sequence) on the front of the
TCC2/TCC2P/TCC3 card. This activity begins immediately after you close the latches in
It is possible to close the latches/ejectors when the card is not completely plugged into the back
panel of the shelf assembly. Ensure that you cannot insert the card any farther.
a
to verify the LED activity on the TCC2 card. For the TCC2P go to Step b. For
All LEDs turn on briefly. The red FAIL LED and the yellow ACT/STBY LED turn on for about
15 seconds. (For TCC3 card it takes around 20 to 25 seconds)
The red FAIL LED and the green ACT/STBY LED turn on for about 40 seconds.
The red FAIL LED blinks for about 15 seconds.
The red FAIL LED turns on for about 15 seconds. All LEDs turn on for about 3 seconds before
turning off for about 3 seconds.
Both green PWR LEDs turn on for 10 seconds. The PWR LEDs then turn red for 2 to 3 minutes
before going to steady green.
While the PWR LEDs are red for two to three minutes, the ACT/STBY turn on.
The boot-up process is complete when the PWR LEDs turn green and the ACT/STBY remains
on. (The ACT/STBY LED will be green if this is the first TCC2 card installed, and amber if this
is the second TCC2 card installed.)
It might take up to four minutes for the A and B power alarms to clear.
Alarm LEDs might be on; disregard alarm LEDs until you are logged into CTC and can view the
Alarms tab.
If you are logged into CTC, the SFTWDOWN alarm might appear as many as two times while
the TCC2 card initializes. The alarm should clear after the card completely boots.
If the FAIL LED is on continuously, see the tip in
Chapter 1
Install the Cisco ONS 15454 Shelf Assembly
Step 8
about the TCC2 card automatic upload.