Chapter 1
Install the Cisco ONS 15454 Shelf Assembly
Step 7
Terminate the return 1 lead to the RET1 backplane terminal. Use oxidation-prevention grease to keep the
connections noncorrosive.
Terminate the negative 1 lead to the negative BAT1 backplane power terminal. Use oxidation prevention
Step 8
grease to keep connections noncorrosive.
If you use redundant power leads, terminate the return 2 lead to the positive RET2 terminal on the
Step 9
ONS 15454. Terminate the negative 2 lead to the negative BAT2 terminal on the ONS 15454. Use
oxidation-preventative grease to keep connections noncorrosive.
Route the cables out below the power terminals using the plastic cable clamp, as shown in
Step 10
on page
Return to your originating procedure (NTP).
Step 11
DLP-G19 Turn On and Verify Office Power
Purpose
Tools/Equipment
Prerequisite
Procedures
Required/As Needed Required
Onsite/Remote
Security Level
Caution
Do not apply power to the shelf assembly until you complete all installation steps.
Step 1
Using a voltmeter, verify the office battery and ground at the following points on the fuse and alarm
panel:
a.
b.
Step 2
To power up the node, insert the fuse into the fuse position according to site practice. The fuse rating
must not exceed 30A.
78-19286-01
1-38.
This task measures the power to verify correct power and returns for the ONS
15454 shelf.
Voltmeter
ETSI:
Connect the office ground to chassis. For detailed instructions on
grounding, refer to the
Grounding
DLP-G17 Connect Office Power to the ONS 15454 ETSI, page 1-35
DLP-G18 Connect Office Power to the ONS 15454 ANSI, page 1-37
Onsite
None
To verify the power, place the black test lead of the voltmeter to the frame ground. Place the red test
lead on the A-side connection and verify that it is between –40.5 VDC and –57 VDC. Place the red
test lead on the B-side connection and verify that it is between –40.5 VDC and –57 VDC.
Note
The voltages –40.5 VDC and –57 VDC are, respectively, the minimum and maximum
voltages required to power the chassis. The nominal steady-state voltage is -48 VDC.
To verify the ground, place the black test lead of the voltmeter to the frame ground. Place the red
test lead on the A-side return ground and verify that no voltage is present. Place the red test lead on
the B-side return ground and verify that no voltage is present.
Cisco ONS Electrostatic Discharge (ESD) and
Guide.
Cisco ONS 15454 DWDM Procedure Guide, Release 9.2
Required Tools and Equipment (ETSI)