Panasonic S-3650PU3E Technical Data & Service Manual page 42

Hide thumbs Also See for S-3650PU3E:
Table of Contents

Advertisement

1
1-5. Capacity Correction Graph According to Temperature Condition
PZ3
U-71PZ3E5 (For 50 Hz)
Cooling capacity ratio (maximum capacity)
160
140
120
100
80
60
40
20
160
140
120
100
80
60
40
20
-15
-5
Outdoor air intake temp ( °C DB)
Outdoor unit heating capacity correction cofficient during of frosting/defrosting
Outdoor intake air
-16
temperature °C WB
0.935
Correction coefficient
To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
Indoor air intake temp (°C WB)
Indoor air intake temp (°C WB)
5
15
25
35
-15 -14 -13 -12 -11 -10 -9
0.934
0.933
0.932
0.931
0.930
0.923
0.917
Heating capacity ratio (maximum capacity)
160
140
120
22℃
100
19℃
80
16℃
60
40
20
160
140
22°C
120
19°C
16°C
100
80
60
40
20
45
-20
-15
Outdoor air intake temp ( °C WB)
-8 -7 -6 -5
-4 -3
0.910
0.903
0.896
0.890
0.883
0.876 0.876 0.840 0.870 0.890 0.930 0.950 0.980 0.990 1.000
1-5-4
Indoor air intake temp (°C DB)
Indoor air intake temp (°C DB)
-10
-5
0
5
10
-2
-1
0
1
2
3
4
24°C
20°C
16°C
24°C
20°C
16°C
15
20
5
6