Connecting Tubing Between Indoor and Outdoor Units
(1) Tightly connect the indoor-side refrigerant tubing extended from the wall with the outdoor-side tubing.
Indoor Unit Tubing Connection
Indoor unit type
S-3650PF3E
Gas tube
ø12.7
Liquid tube
ø6.35
Different-diameter-tube joint for the indoor unit tubing connection part is supplied with S-6071PF3E.
The size of parenthesis indicates the connection tube diameter when using the different-diameter-tube joint.
How to use different-diameter-tube joint (supplied)
1) When using with single connection
• Outdoor PZ3 series (Type 60)
Connect the liquid socket tube B (ø6.35 - ø9.52)
to the liquid tubing side indoor unit
Liquid tube (ø6.35)
Gas tube (ø12.7)
Connect the gas socket tube A (ø12.7 - ø15.88)
to the gas tubing side indoor unit
• Outdoor PZ3 series (Type 71)
Liquid tube (ø6.35)
Gas tube (ø15.88)
Connect the liquid socket tube B (ø6.35 - ø9.52)
to the liquid tubing side indoor unit
(2) To fasten the flare nuts, apply specified torque.
When removing the flare nuts from the tubing connections, or when tightening them after connecting the tubing,
be sure to use two spanners. When tightening the flare nuts, use a torque wrench.
If the flare nuts are over-tightened, the flare may be damaged, which could result in refrigerant leakage and
cause injury or asphyxiation to room occupants.
Torque wrench
Indoor unit
Outdoor unit
Unit : mm
S-6071PF3E
ø15.88
ø9.52
Spanner
1-11-1-2-24
1