Panasonic S-3650PU3E Technical Data & Service Manual page 226

Hide thumbs Also See for S-3650PU3E:
Table of Contents

Advertisement

Alarm
Code
E01
Remote Controller Reception Error
E02
Remote Controller Transmission Error
E03
Error in Indoor Unit Receiving Signal from Remote Controller (central)
E04
Error in Indoor Unit Receiving Signal from the Outdoor Unit
E08
Duplicate Indoor Unit Address Settings Error
E09
More Than One Remote Controller Set to Main Error
E12
Auto Address Setting Start is Prohibited while Auto address Setting in Progress.
E14
Main Unit duplication in Simultaneous-operation Multi Control (detected outdoor unit)
E15
Auto Address Alarm (The total capacity of indoor units is too low.)
E16
Auto Address Alarm (The total capacity of indoor units is too high or the total number of indoor units is too many.)
E18
Faulty Communication in Group Control Wiring
F04
Compressor Discharge Temperature Sensor (TD) Trouble
F06
Inlet Temperature Sensor (C1) in Heat Exchanger Trouble
F08
Outdoor Air Temperature Sensor (TO) Trouble
4
H01
Primary (input) Overcurrent Detected
H02
PAM Trouble
H03
Primary Current CT Sensor (current sensor) Failure
L18
4-Way Valve Operation Failure
P03
Compressor Discharge Temperature Trouble
P04
High Pressure Trouble
P05
AC Power Supply Trouble
P07
HIC (IPM) Temperature Trouble
P09
Faulty wiring connections of (ceiling) indoor unit panel
P13
Alarm Valve Open
P15
Insufficient Gas Level Detected
P16
Compressor Overcurrent Trouble
P22
Outdoor Unit Fan Motor Trouble
P29
Lack of INV compressor wiring, INV compressor actuation failure (including locked), DCCT failure
P31
Group Control Error
Alarm Meaning
4-21