Outdoor; Inspection Of Parts (Outdoor Unit) - Panasonic S-3650PU3E Technical Data & Service Manual

Hide thumbs Also See for S-3650PU3E:
Table of Contents

Advertisement

5-3. Inspection of Parts (Outdoor Unit)

(1) Electronic control valve (MOV1)
STM/STM1: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN-STM/CN-STM1 connector
(white)
Set the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage is normal.)
If the voltage is normal, measure the resistance between connector pin 5 and pins 1 through 4.
Resistance between pin 5 and pins 1 through 4 should be approximately 46 Ω for all. (If the result is 0 Ω or,
then replace the coil.)
(2) Outdoor Unit Fan Motor
Model No.
U-36PZ3E5
U-50PZ3E5
U-60PZ3E5
U-71PZ3E5
(3) Coil Resistance of Compressor
Model No.
(Panasonic)
U-36PZ3E5
ACXB09-03470
U-50PZ3E5
ACXB09-04960
U-60PZ3E5
ACXB09-04940
U-71PZ3E5
ACXB09-04950
Part No. (Panasonic)
L6CAYYYL0064
L6CAYYYL0064
L6CAYYYL0076
L6CAYYYL0076
Part No.
Part No.
9RS102XFA21
9RD132XAB21
9RD132XAA21
9KD240XBA21
Part No.
NFD-52FV-D840-16
NFD-52FV-D840-16
NFD-62FV-D840-6
NFD-62FV-D840-6
Inverter compressor (at 20°C)
U - V
V - W
1.211
1.211
1.897
1.882
1.897
1.882
0.720
0.708
5-3-1
U - W
1.211
1.907
1.907
0.726
5