Outdoor - Panasonic S-3650PU3E Technical Data & Service Manual

Hide thumbs Also See for S-3650PU3E:
Table of Contents

Advertisement

Check Prior to Auto Address Setting
* If an outdoor unit displays an alarm, conduct this process after diagnosing the problem.
1 Auto
Address
1-1
Is the power of the indoor unit(s) and outdoor unit(s) on?
Indoor/
2
Has the wiring of the indoor/outdoor been completed?

outdoor

2-1
Is it all connected correctly?
wiring
3
Installation
Be sure that the indoor and outdoor units are connected
or setting
3-1
with correct combination written in catalog.
related
Is the remote control wiring connected with two indoor/outdoor
3-2
combinations or more for group control?
Turn on the power of only one system and run auto address setting again. Upon completion of
the auto address setting, turn on the power for the next system and run auto address setting
3-3
while still power switched on, units whose auto address setting have completed. (In the case
of multiple systems, run the auto address setting respectively in due order for each system.)
3-4
Run the auto address setting.
4
Relocation
Be sure that the indoor and outdoor units are connected with
4-1
and resetting
correct combination described in the catalog.
of address
4-2
Be sure that the detailed setting items are made at factory setting.
[ U3, F3 ]
4-3
Run the auto address setting.
For information on the remote control's detailed settings, refer to the Reference Materials.
Factory setting
Item code
11
Indoor unit capacity
12
System address
13
Indoor unit address
14
Group conrol address
Item
Value
5-2-1-2
0
99
99
99
Yes
2-1
No
Power on
3-1
Yes
Connect the wiring
No
correctly
Yes
3-2
No
Correct the connection
Yes
3-3
No
3-4
Yes
4-2
No
Correct the connection
Yes
4-3
No Correct the setting
5