Drawing the DRIVE-CLiQ connection
A DRIVE-CLiQ connection is drawn between two DRIVE-CLiQ ports.
1. Left-click the output port and keep the mouse button pressed.
Figure 4-14
2. Drag the line displayed to the target port.
A connection is established between the two ports. The connection is indicated using a
blue line.
4.4.5.6

Making detailed settings

During commissioning, generally the device supply voltage and, when ALMs are used, also
the used line filters can be parameterized.
Following automatic commissioning, the appropriate filter for the matching Active Interface
Module is pre-selected as the line filter. If the drive line-up is set up differently, then the line
filter type must be adjusted.
When first switched on with a new/modified network, an automatic controller setting must be
implemented using the line and DC link identification routine (p3410). While the identification
routine is running, it is not permissible for other loads to be switched in/switched out.
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0
Drawing the DRIVE-CLiQ connection
4.4 Creating a project offline in Startdrive
Commissioning
97