Commissioning
4.10 Commissioning a drive
Deactivating the control panel
When you deactivate the control panel, you return the master control.
To deactivate the control panel, proceed as follows:
1. Click the "Off" button to switch off the drive.
This is a basic requirement for deactivating the control panel.
2. Click "Deactivate" at "Master control".
The grayed-out user interface of the control panel shows that the master control has been
deactivated.
Setting the enable
To set the required enable for the control panel, proceed as follows.
1. Click "Set" at "Drive enables".
Further areas of the control panel are activated.
2. Click "Acknowledge faults" to acknowledge the currently pending faults.
3. If you no longer require the enables, click "Reset" at "Drive enables".
Result
You can now traverse the drive with the control panel. Enables and faults are displayed at
"Drive status". In addition to "Active fault", the currently pending fault is displayed.
4.10.2

Traversing the drive with speed specification

After you have set the drive enables, in the "Control Panel" screen form specify the operating
mode and switch on the motor.
206
Commissioning with Startdrive
Commissioning Manual, 12/2018, 6SL3097-5AA10-0BP0