Operation
6.1.1

LEDs

Note!
To save battery power all LEDs are off during normal operation, even if the device is
communicating or joining the network. The LEDs only light up after start up or while
pressing the buttons.
When the pushbutton is pressed shortly (0.2 s ... 5 s), the three LEDs indicate the status of
the adapter (see chapter 6.1.2).
LED indicators
Number of LEDs
Indications of green LED (battery status)
LED on
LED flashes at 1 Hz
LED flashes at 3 Hz
LED off
Indications of yellow LED (communication status)
LED on
LED flashes at 1 Hz
LED flashes at 3 Hz
LED off
Indications of red LED (device status)
50 ms on
950 ms off
LED on
LED flashes at 1 Hz
LED flashes at 3 Hz
LED off
3 (green, yellow, red)
Status "Normal": At least one month of battery life is left.
Status "Warning": Less than one month of battery life is left.
Status "Alarm": The battery is critically low, loop power cannot be
supplied.
Any current signal cannot be read (4 ... 20 mA device).
The adapter still operates, but the connection is not assured.
Status "Off": The battery is flat or disconnected.
Status "Joined, alternative path": The device was has full network
connection. It is able to communicate with at least 2 wireless nodes. At
least one alternative communication path to the gateway is available.
Status "Joined, no alternative path": The device was able to join the
network. However, it can communicate with a single wireless node only.
There is no alternative communication path to the gateway.
Status "Joining": The device is attempting to join the network. The adapter
will attempt to join for 40 minutes by default. Longer joining periods can be
configured if required.
"Not joined" mode: Joining the network has failed. The device is no longer
attempting to join.
Device in communication mode: It is possible to communicate with the
adapter.
Status "Internal fault": Device fault that cannot be remedied by the user.
Status "External fault": Operative fault which can possibly be remedied by
the user:
Adapter temperature outside specified limits,
Measured value outside configured range.
Operative faults can be viewed with the Diagnosis function of the DTM.
Status "Short-circuit": There is a short-circuit between terminals 1 and 2.
No fault