WHA-ADP-*
Installation
3.3.2

Connecting Cables

Required tools:
Phillips screwdrive PZ1 to open the adapter cover,
Screwdriver with 2.5 mm blade to make the connections.
If the adapter is mounted on the field device, use the two wires supplied to make the
connection.
If the adapter is to be mounted separately, standard installation cable can be used. If strong
electromagnetic interference is to be expected (machines, walkie-talkies), use shielded,
twisted pairs. Connect the shield to the ground terminal.
1
Figure 3.14: Opening the cover
1
Captive screws
Figure 3.15: Cable entries
1
Primary cable entry (blind plug seals adapter when cable entry not in use)
2
Secondary cable entry with M20x1.5 cable gland
1