Wiring Power Modules - YASKAWA VIPA SLIO FM 050-1BB00 Manual

Counter module 2x32bit
Table of Contents

Advertisement

Basics and mounting

Wiring power modules

2.6 Wiring power modules
Terminal module terminals
Data
Wiring procedure
20
Power modules are either integrated to the head module or may be installed between the
periphery modules. With power modules, terminals with spring clamp technology are
used for wiring. The spring clamp technology allows quick and easy connection of your
signal and supply lines. In contrast to screw terminal connections this type of connection
is vibration proof.
U
30V DC
max
I
10A
max
Cross section
0.08 ... 1.5mm
Stripping length 10mm
1
Pin number at the connector
2
Opening for screwdriver
3
Connection hole for wire
1.
Insert a suited screwdriver at an angel into the square opening as shown. Press
and hold the screwdriver in the opposite direction to open the contact spring.
2.
Insert the stripped end of wire into the round opening. You can use wires with a
cross section of 0.08mm
3.
By removing the screwdriver, the wire is securely fixed via the spring contact to the
terminal.
2
(AWG 28 ... 16)
2
2
up to 1.5mm
HB300 | FM | 050-1BB00 | en | 19-38
VIPA System SLIO

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vipa slio fm 050

Table of Contents