HB300 | FM | 050-1BB00 | en | 19-38
Aborting gate control:
Main counting direction forward
The counter counts starting with the load value.
n
n
When the counter reaches the end value -1 in positive direction, it jumps to the load
value at the next positive count pulse and the gate is automatically closed.
n
To restart the count process, you must create a positive edge of the gate. The counter
starts with the load value.
Limits
Limit value
Lower count limit
Main counting direction backwards
n
The counter counts backwards starting with the load value.
n
When the counter reaches the end value +1 in negative direction, it jumps to the load
value at the next negative count pulse and the gate is automatically closed.
n
To restart the count process, you must create a positive edge of the gate. The counter
starts with the load value.
Valid value range
31
-2 147 483 647 (-2
+1)
31
to +2 147 483 647 (2
-1)
31
-2 147 483 648 (-2
)
Deployment
Counter - Functions
49