System Installation
DS1000 Electrical Specifications
DS2000 Electrical Specifications
Power Requirements
42
DS1000/2000 Workbook
Power Supply:
Output Power
Input Current
VA
Kwh
BTU
Grounding Requirements:
Power Supply:
Output Power
Input Current
VA
Kwh
BTU
Power Requirements:
Grounding Requirements:
A dedicated 110 VAC 60 Hz circuit is required. For the DS1000, this must be
within 4 1/2 feet of the cabinet. For the DS2000, it must be located within seven
feet of the cabinet. You should install a separate dedicated outlet for each cabinet.
120 VAC ± 10% @ 50-60 Hz
35 Watts
550 mA
66 VA
.066 KwH
225 BTU
12 AWG copper wire
120 VAC ± 10% @ 50-60 Hz
91 Watts @ 100% full load
1.50A @ 110V
165
.165
563
120 VAC @ 1.5A (180 VA) max. per cabinet
12 AWG copper wire