8.11 Test Function for Analog Output

In this menu, you can define a desired value in mA for the analog output in order to test its function. This value
is then directly available at the output.
This menu is only available in special mode.
The manual operation has priority over the activation by the gas concentration.
The testing is possible via code level 1, 3 and 4.
When the menu is exited, the actual current signal is immediately output again, the entry field shows 0.
The test function is only possible for an active analog output.
Analog Output
Test Function
®
PolyGard
is a registered trademark of MSR
Phone 0049(0)8531/9004-0
Fax: 0049(0)8531/9004-54
MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
®
2
Default
Function
X = 1 – 5 Select the relay
Status OFF
OFF
Status ON
Alarm manual ON
Alarm manual OFF
Autom
Automatic
AO 1
Preset
4.02 mA
0.00 mA
AO 1
Set Value
4.02 mA 12.00 mA
AO 1
Set Value
12.00 mA 12.00 mA
Page
32
= Relay off (no gas alarm)
= Relay on (alarm)
= Relay manually set in alarm status
= Relay manually set in "no alarm" status
= Reset of manual intervention, relay
in automatic mode
On the left you can see the current set-point
as calculated from the gas concentration.
Enter the required current under "Set Value",
e.g. 12 mA
The set value is accepted as set-point
(by displaying it on the left)
and is physically output.