8.10 Test Function for Relays

In this menu, the alarm relays can be manually turned on and off in order to test their function.
This menu is only available in special mode.
The manual operation takes priority over activation by a gas alarm. However, the external activation of the
alarm relays via a digital input takes priority over the manual test function.
The test mode simulates an alarm for the relay and the relay accepts the alarm status. The test function is
deleted by selecting "Automatic" or by exiting the Special Mode.
The testing is possible via code level 1, 3 and 4.
Selection of the relay 1 - 5
Relay
Test Function
®
PolyGard
is a registered trademark of MSR
Phone 0049(0)8531/9004-0
Fax: 0049(0)8531/9004-54
MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
®
2
Sensitivity
100%
Maintenance Days
Last
xxx
Days of operation
Last
xxx
Maintenance Days
Currently
xxx
Max. Current Value
0
Relay X
Status
OFF
Selection of further
relays
Page
31
Sensitivity of the analog sensor at the
last calibration compared to
new sensor (only for analog sensors)
Display of the days differing from
the nominal maintenance date
(fixed value)
Days of operation since the last
calibration (fixed value)
Currently remaining days until
next maintenance date
(down counter)
Maximum measured current
value of the sensor head
Relay
1
Alarm manual ON
Relay
1
Alarm manual OFF
Relay
1
Automatic