8.8.6 AO Function

This menu is for the configuration of the analog output.
After registration, each analog output checks the current signal for plausibility. Signal deviations of more than
5% from the nominal value will generate an error message (causes: short circuit or interruption of cable,
actuator not connected).
The steepness of the current signal can be adjusted in the range of 10 to 100% in case of local control.
If several measuring points are assigned, you can define whether the minimum, the maximum or the average
of all the assigned signals is output. It is likewise possible to define which signal of the measuring points
(source) is output.
If the 4 - 20 mA signal is used as a safe signal (SIL level), the following mandatory parameters must be
used:
Selection of analog signal:
Selection source:
Selection of operating mode:
Symbol
Description
Analog
Selection of
Output 1
channel
0
Selection of
output signal
10-100 %
Selection of
C
source
Selection of
Max.
mode
Note: If you use more than one oxygen sensor, please do not use the mA output function; please
use only the relay functionality.
®
PolyGard
is a registered trademark of MSR
Phone 0049(0)8531/9004-0
Fax: 0049(0)8531/9004-54
MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
®
2
AO Function
100:
100 % gas signal = 20 mA (standard signal)
CF:
Source current value signal with fault message
Max: Output of the maximum value of the assigned MP
Default
Function
Selection of the analog output 1 - X
0 = Analog output is not used, no monitoring of the feedback
≥ 10 = Local control and definition of the signal slope
100 %
10 = 10 % gas signal = 20mA (high sensitivity)
100 = 100 % gas signal = 20mA (standard signal)
C = Source is current value
A = Source is average value
A
CF = Source is current value and additional fault message at AO
AF = Source is average value and additional fault message at AO
Min.
= Displays the minimum value of all assigned MP
Max.
Max.
= Displays the maximum value of all assigned MP
Average = Displays the average value of all assigned MP
Page
28
Analog Output
1
100 %
C
Max.
GAMGC2-K_E_0320