8.6.7 Delay Mode of Alarm Relay

.
Relay 3:
The parameter setting cannot be changed.
Definition of the time for switch-on and switch-off delay of the alarm relays.
Symbol
Description
Switch-ON
0 sec.
Delay Time
Switch-OFF
0 sec.
Delay Time

8.6.8 Assignment to Fault

Relay 3:
The parameter setting cannot be changed.
In case of a device fault the alarm, relay is triggered in addition.
This relay output must not be used as a safe error output.
Symbol
Description
No
No assignment No
Assignment to
Yes
fault

8.6.9 Assignment to Maintenance Message

In case of a pending maintenance, the alarm relay is triggered in addition.
Symbol
Description
No
No assignment No
Assignment to
Yes
maintenance
®
PolyGard
is a registered trademark of MSR
Phone 0049(0)8531/9004-0
Fax: 0049(0)8531/9004-54
MSR-Electronic GmbH, Bgm.-Schoenbauer-Str. 13, D 94060 Pocking www:msr-electronic.de Made in Germany
®
2
Default
Function
≥ 1: Alarm relay is only activated at the end of the defined time.
0
0 = No delay
≥ 1: Alarm relay is only deactivated at the end of the defined time.
0
0 = No delay
Default
Function
Alarm relay is not activated in case of a device fault.
Yes
Alarm relay is activated in case of a device fault.
Default
Function
Alarm relay is not activated in case of a maintenance message.
Yes
Alarm relay is activated in case of a maintenance message.
Page
19
On Delay Time
0 s
Off Delay Time
0 s
Fault→ Active
No
Maintenance→ Active
No
GAMGC2-K_E_0320