Pipe Installation For The Condensate Water System - Gree GMV5 Series Service Manual

Dc inverter vrf units
Hide thumbs Also See for GMV5 Series:
Table of Contents

Advertisement

Gas pipe filter
Added stop valve
for the gas pipe
II. Pipe Installation for the Condensate Water
System
1. Pipes
Generally, U-PVC water supply pipes bonded with special glue are adopted as condensate water
pipes. PP-R, PP-C, and hot galvanized steel pipes can also be adopted. Aluminium plastic compound
pipes cannot be used.
2. Requirements on Installation
2.1 Determine the direction and elevation of a condensate water pipe before installing it. Avoid
overlapping it with other pipes to ensure straight inclination. The clamp of the pipe hanger is fixed
outside the insulation layer. The height of the clamp can be adjusted.
2.2 Distance between Hangers
There are at least two hangers for each vertical pipe.
2.3 The inclination degree of the condensate water pipe must be above 1% and that of the main pipe
cannot be lower than 0.3%. Adverse slopes are not allowed.
2.4 When connecting three-way pipes, the two-way straight pipes must be laid on the same slope, as
shown in the following figures.
2.5 The condensate water pipe cannot be tied with the refrigerant pipe.
2.6 A ventilation hole must be provided on the top of the drain pipe to ensure smoother discharge of
condensate water.
GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
Stop valve equipped
to the outdoor unit
for the gas pipe
Stop valve equipped
to the outdoor unit for
the liquid pipe
Drier filter for the liquid pipe
Added stop valve
for the liquid pipe
External Diameter of
the Pipe (mm)
Distance between
Horizontal Pipes (mm)
Distance between
Vertical Pipes (mm)
Φ≤25
32>Φ≥25
800
1000
1500
62
Φ≥32
1500
2000