Gree GMV5 Series Service Manual page 94

Dc inverter vrf units
Hide thumbs Also See for GMV5 Series:
Table of Contents

Advertisement

Step 4: When the high-pressure value displayed on LED3 continually blinks (displayed as 0C if the high
pressure is less than 0C), quickly close the air-tube stop valve of the emergency module and then press
"SW7" on the master unit to confirm completing refrigerant recovery or power off the entire unit.
If no operations are performed after the high-pressure value displayed on LED3 continually blinks for
three minutes, the entire unit will be forcibly stopped.
On the master unit, press "SW6" to return to the upper level for restoring the standby status of the entire
unit (press "SW6" in setting status to return to the upper level; press "SW6" after settings are completed
to restore the normal operating status of the unit).
Note:
Before the basic module refrigerant recovery operation, users must close the liquid-tube stop
valve of the basic module requiring refrigerant recovery.
Another startup is not allowed within 10 minutes after refrigerant recovery.
 A8 Aftersales vacuuming mode settings
Step 1: Confirm entering the A8 aftersales vacuuming mode settings. The master unit is displayed as
follows:
Function
Code
Enter the to-be-confirmed status of system vacuuming mode settings.
Step 2: Press "SW7" to confirm entering the to-be-confirmed status of system vacuuming mode settings.
All modules are displayed as follows:
Function
Code
Expansion valves and electromagnetic valves of all outdoor and IDUs are opened, and the entire unit
cannot be enabled.
Press "SW6" on the master unit to quit the vacuuming status. Alternatively, the entire unit quits the
vacuuming status after 24 hours.
 n0 System conservation operation settings
Step 1: Confirm entering the n0 system conservation operation settings. The master unit is displayed as
follows:
LED1
Function Code Display Mode Code Display Mode Current Status Display Mode
n0
Step 2: Select a corresponding mode by pressing "SW1 (UP)" or "SW2 (DOWN)".
LED1
Function Code Display Mode Code Display Mode Current Status Display Mode
n0
n0
Step 3: Press "SW7" to confirm selecting the mode. The master unit is displayed as follows:
LED1
Function Code Display Mode Code Display Mode Current Status Display Mode
n0
n0
If no button operations are performed for five minutes, the function setting automatically quits and the
unit restores the current status. (Press "SW6" in setting status to return to the upper level; press "SW6"
GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
LED1
Display
Current
Mode
Progress
A8
On
LED1
Display
Current
Mode
Progress
A8
On
On
01
On
01
On
02
On
01
On
02
LED2
Display
Current
Mode
Status
00
Blinking
LED2
Display
Current
Mode
Status
00
On
LED2
Blinking
LED2
Blinking
Blinking
LED2
On
On
91
LED3
Display
Mode
OC
Blinking
LED3
Display
Mode
OC
On
LED3
OC
Blinking
LED3
OC
Blinking
OC
Blinking
LED3
OC
On
OC
On

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents