R410A Refrigerant System
Y-type Manifold
(6).
Fitting pipe between manifolds
Pipe size (between two manifolds at indoor unit side) is based on the total capacity of upstream
indoor unit(s).
Total Rated Capacity X(kW) of
Downstream Indoor Units
(7). Fitting pipe between indoor unit and manifold
Manifold should be matched with fitting pipe of indoor unit.
GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
Total capacity of downstream indoor unit(s) C
X≤5.6
5.6<X≤14.2
14.2<X≤22.4
22.4<X≤28.0
28.0<X≤40.0
40.0<X≤45.0
45.0<X≤68.0
68.0<X≤96.0
96.0<X≤135.0
135.0<X
(kW)
C≤20.0
20.0 <C≤30.0
30.0<C≤70.0
70.0<C≤135.0
135.0<C
Fitting Pipe Size between Indoor Manifolds
Gas Pipe (mm)
Φ12.7
Φ15.9
Φ19.05
Φ22.2
Φ25.4
Φ28.6
Φ28.6
Φ31.8
Φ38.1
Φ44.5
53
Model
FQ01A/A
FQ01B/A
FQ02/A
FQ03/A
FQ04/A
Liquid Pipe (mm)
Φ6.35
Φ9.52
Φ9.52
Φ9.52
Φ12.7
Φ12.7
Φ15.9
Φ19.05
Φ19.05