Gree GMV5 Series Service Manual page 109

Dc inverter vrf units
Hide thumbs Also See for GMV5 Series:
Table of Contents

Advertisement

6) The following table describes progress display of each phase during commissioning:
Commissioning
——
Progress
Code
db
db
01_Master
unit setting
detection
db
db
db
02_Unit
address
assignment
db
db
03_Basic
module
db
quantity
confirmation
for ODU
db
db
04_Indoor
unit quantity
confirmation
db
db
05_Internal
communicati
on detection
for basic
db
modules
db
db
GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
Progress Description for Commissioning Phases
Code
Progress Code
LED1
LED2
Display
Display
Status
Code
Status
On
01
On
01
On
01
On
01
On
02
On
02
On
02
On
03
On
03
On
04
On
04
On
05
On
05
On
05
On
05
Status Code
LED3
Code
On
A0
On
CC
On
CF
On
OC
On
Ad
On
L7
On
OC
On
01-04
On
OC
On
01-80
On
OC
On
C2
On
C3
On
CH
On
CL
106
Display
Status
Meaning
The system is in
non-commissioning
On
status.
The system does not set
any master unit, and a
master unit should be
On
set.
The system sets more
than two master units,
and a master unit should
On
be set again.
The system successfully
sets a master unit and
automatically enters the
On
next step.
The system is assigning
Blinking
addresses.
There is not any master
IDU, and a master IDU
should be set through the
commissioning software.
If no master IDU is set
within one minute, the
system will automatically
Blinking
set one.
The system successfully
assigns addresses and
automatically enters the
On
next step.
LED3 displays the
module quantity, which
should be manually
Blinking
confirmed.
The system confirms the
module quantity and
automatically enters the
On
next step.
LED3 displays the IDU
quantity, which should
Blinking
be manually confirmed.
The system confirms the
IDU quantity and
automatically enters the
On
next step.
The system detects
communication failure
between master unit and
inverter compressor
On
driver.
The system detects
communication failure
between master unit and
On
inverter fan driver.
The rated capacity ratio
is over-high between
On
IDUs and ODUs.
The rated capacity ratio
On
is over-low between