Advertisement

5.2 Preliminary Check
Check the server for network interface. If it does not have network interface, replace it with one that has
network interface. The network interface will ensure normal communication between the server and
BACnet and client.
Check the adapter and check whether server is connected to a LAN. If not, connect it to the LAN so that
the client can communicate with the server.
Check whether the BACnet gateway has been successfully debugged. If not, refer to the Technical
Service Manual of BACnet Gateway to debug BACnet gateway.
Check whether the server is configured with driver that can read disks.
Check whether the server satisfies the following software configuration requirements.
Part Name
Internet Information
Service (IIS) manager
MSMQ
Memory
Hardware
CPU
OS
Note
Gree CAC Remote Monitoring System supports Windows Server 2003 SP2 or later versions and
Windows 7. Windows Server 2003 SP2 is recommended because the server can better provide users
with services in Windows Server 2003 SP2 system.
5.3. Software Setup
The software needs support of some Windows components in order to run; therefore, you should install
these components first before setup. The following installation flowchart shows you the basic installation
procedure. If some of the components have been available on your PC, you can skip corresponding
steps.
GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
Min. Configuration
6.0 or later versions
/
1 GB or larger
10 GB available
Main frequency: 2 GHz or higher
Windows Server 2003 SP2 or
later versions, Windows 7
341
Recommended
Configuration
6.0
/
2 GB or larger
10 GB available
2 GHz or higher
Windows Server
2003 SP